Technnical Data

Voltage

Static:+1%
  
Dynamic: a) at change of nominal load, cos-phi = 0,8,: +10%, voltage comeback within 0,3 seconds.
b) Short circuit at the input +/- 10%. Voltage tolerance after short circuit shut down < 10% within 0,3 seconds.
c) Mains shutdown at nominal voltage +10% within 0,3 seconds
  
Frequency: a) at grid operation = grid frequency.
b) change grid to diesel operation at takeover of 100 % load +1%.
c) static – at diesel operation +0,5%.


When desired other tolerances are possible!
Leerzeile

Mechanical Design

Leerzeile
1) Diesel engine
2) Electromagnetic clutch
3) Synchronous machine
4) Kinetic Module
12) Flexible clutch